Troubleshoot MUX CPU Fail
Troubleshoot MUX CPU Fail
Cause
The panel is displaying a MUX CPU FAIL. Is the panel or MUX Driver Card bad?
Solution
If the panel is wired Class A on the Multiplex Buss Check the Buss for a short - A short, ground or noise on the Class A loop will cause a CPU FAIL to be displayed on the Panel.
If there is not a short, ground or noise on the mux loop or the panel is wired Class B then do the following:
- Power down the panel completely
- Remove all MUX field wiring from the card
- Remove the MUX Driver Card
- Inspect the Pins and Socket for damage
- Reset the card Repower the panel - if the MUX CPU FAIL is still present, Try defaulting the panel -If the CPU fail is still present replace the panel and MUX Driver Card.
Part numbers FPD-7024, D7024, DS9400, DS9400I, DS9400M, DS9431, D7039, FPE-7039
Related content
Troubleshoot MUX A Wire Fail or Wiring Fault
Troubleshoot MUX A Wire Fail or Wiring Fault
More like this
How to troubleshoot missing D8125 Mux devices.
How to troubleshoot missing D8125 Mux devices.
More like this
Verify if the Panel is Communicating with the MUX Card
Verify if the Panel is Communicating with the MUX Card
More like this
How to Troubleshoot the Multiplex Bus Troubles on DS7400 Series
How to Troubleshoot the Multiplex Bus Troubles on DS7400 Series
More like this
Add or Install Mux Devices to DS9400 & 7024 Series FACP
Add or Install Mux Devices to DS9400 & 7024 Series FACP
More like this
͏ ͏ Stay up to date |
Get in touch |
You are on |
---|---|---|
Bosch Building Technologies
|
͏ ͏ Corporate information |
Legal Notice |
Data Protection Notice |
California Privacy |
CCPA-and-Canadian-Privacy-Disclosure |
Terms of use |