Do Bosch addressable smokes and smoke bases support CleanMe functions?
Do Bosch addressable smokes and smoke bases support CleanMe functions?
Question
Do Bosch addressable smokes and smoke bases support CleanMe functions?
Answer
Currently the only Bosch smoke detector that supports CleanMe functions is the F220 series smoke heads when used with a conventional two-wire (F220-B6) base only and a CleanMe enabled control panel such as the D7024, and FPD-7024 conventional zones.
Note: The D7050, D7050TH does have a Chamber Check feature that will report dirty smoke if the head needs cleaning when used on the D7024, FPD-7024, DS9400m, DS9400, DS9400i.