How to Troubleshoot Blown Panel Transformor D1640

How to Troubleshoot Blown Panel Transformor D1640

Issue

Transformers on panels continue to blow after connecting to panel that has be without power for a day or more.
 
Solution
 

Battery backup on panel has developed internal short on it which causes panel to over draw current. Replace defective battery / batteries.

Part numbers D7212B, D9112B, D7212B1, D9112B1, D7212, D7412, D9112, D9124, D9412, D7212G, D7412G, D7412G, D9124G, D9412G, D7212GV2, D7412GV2, D7412GV2, D9124GV2, D9412GV2, D7212GV3, D7412GV3,D7412GV3, D9412GV3, D7212GV4, D7412GV4, D7412GV4, D9412GV4, B8512G, B9512G