How the Troubleshoot D192G Trouble with Yellow LED Off

How the Troubleshoot D192G Trouble with Yellow LED Off

 

Issue

The D192G panel zone (point) is in trouble and the yellow LED is not on.

Solution

With the zone/point in trouble and No Yellow LED On there is a wiring fault. One of the following terminals do not have power connected to them.

  • External Power In (EXT PWR IN)
  • Auxiliary Power In (AUX PWR IN)

Terminal 1 (AUX PWR IN) 13.75 VDC

Terminal 2 (Common)

Terminal 3 (Supervised Zone / Point) 2.50 VDC Normal Condiction < 1.50 VDC In Trouble Condiction

Terminal 4 (Trigger) 13.75 VDC  In Alarm Only

Terminal 5 (External Power In) 12 VDC or 24 VDC Depended on needed Output for the NAC's or Power Supply

Terminal 6 (Common) This is the Common from an 24 VDC External Power

Terminal 7 (Positive Alarm Output)

Terminal 8 (Negative Alarm Output)