How to Silence RF Low Battery D2212
How to Silence RF Low Battery D2212
Issue
Trouble tones will clear and then return one hour later.
Solution
RF Sensor Low Battery
With earlier revisions of panel firmware, users could silence a low RF fire sensor battery trouble indefinitely. With revision 3.03 (or later), the panel restarts the trouble sounder at the keypad within four hours if the low battery in the fire sensor is not replaced.