How to troubleshoot Invalid Contact ID Signals

How to troubleshoot Invalid Contact ID Signals

Question

What can cause a panel sending Contact ID to produce Data Errors in the receiver?

Answer

Verify the length of the data error. A panel sending contact ID will send 16 digits for the Contact ID signal.
Common causes of the panel not sending the correct number of digits include the following:
 - Voice over IP with Low Sample Rate or Line Compression
 - Line card or Line Terminator Card on the receiver (D6600 only)
 - Panel problem (Corruption, Bad Dialer, etc)
 - Noise on the phone line

There is a checksum value in the Contact ID signal. An incorrect checksum will cause a data error. An invalid checksum value may be caused for the same potential reasons as a dropped DTMF digit (see list above).

Possible fixes for the problem include the following:
 - Reprogram the field panel
 - Swap panel
 - Use a dedicated, analog phone line
 - Swap the Line Card and Line Terminator Card in the receiver
 - Have a qualified telephone technician check the phone line on the site with the panel or at the receiver for problems.

 