How to set up interlock APE

How to set up interlock APE

How to set up Interlock APE

Example Interlock: Door 1 needs to be closed before you can open Door 2.

 

door.png

Note: It only works with 2 Doors.

Example of door configuration:

 

 

Notice: If only one door is defined as part of a door-complex then the synchronization is not active.  

Door #1 configuration:

  • Door #1: Door contact assigned to input#1
  • Output for the maglock assigned to output #1
  • Entrance locked assigned to input #3
  • Input #3 is connected to output #4 (lock opposite direction)
  • When input #1 is opened, it triggers output #3 that is connected to input #4 and it disables reader at Door#2
 

ape2.png

 

The output signal (Out 3) is to be set potential free (dry mode). The signal "door lock of opposite direction" must be closed (resistance=0) when de-energized. Use the "normally closed" (NC) contact of output 3.

ape3.png

 

 

Configuration for Door 2:

  • Door #2: Door contact assigned to input#2
  • Output for the maglock assigned to output #2
  • Entrance locked assigned to input #4
  • Input #4 is connected to output #3 (lock opposite direction)
  • When input #2 is opened, it triggers output #4 that is connected to input #3 and it disables reader at Door#1

 

 

 ape4.png