6026 How to access keypad programming the GV3 Panel.

6026 How to access keypad programming the GV3 Panel.

Keypad programming is available in GV3 panels with firmware revision 8.10 or higher. 
NOTE: Keypad programming is not available during while an RPS programming session is active, or when any area is armed.
Enter from normal operation:
  1. Press [9]+[9]+[Enter].
  2. Select Keypad Programming. The keypad displays Enter Passcode.
  3. Enter the service passcode (default= 123).
Enter from service mode (reset pin closed):
  1. D1255:
    1. Set the address to 16 with dipswitch: 1-5= OFF and 6= ON. The keypad displays Enter Passcode when the reset pin is closed.
    2. Enter the service passcode (default= 123).
  2. D1260:
    1. Set the address to 8 with dipswitch: 1-3= OFF and 4-6= ON. The keypad displays Enter Passcode when the reset pin is closed.
    2. Enter the service passcode (default= 123).
The following options are available upon entering keypad programming:
  • Phone Numbers – Phone 1 thru Phone 4
    • Phone Format - Phone 1 thru Phone 4
    • Enhanced Comm – Path 1 thru 4
  • Routing
    • Route Groups 1 thru 4
  • RPS Parameters
    • RPS Passcode
    • RPS Phone Number
    • RPS IP Address
    • RPS IP Port
  • Area Parameter – 1 thru 32
    • Account On – Yes / No
    • Account Number
  • Command Center 1 thru 16
    • Enhanced Command Center – Yes / No
    • Command Center Scope –
  • User Pass Code
    • User 0 (Install Passcode)
    • User 1 (User Passcode)
  • Point Parameters
    • D9412GV3: 1-247
    • D7412GV3: 1-75
    • D7212GV3 1 -40
    • Point Index
  • Disable Keypad Programming