If FSM needs to be connected to a new panel (network), then proceed as follows:
Step-by-step guide
- In FSM Client / File / Device management / Driver settings
Select the "old" panel to be disconnected and disconnect it (via right mouse click or status drop-down menu) - In Windows Control Panel / Local services
Stop the server - In C:\ProgramData\Alesys\SecurityControlServer\Config\Drivers\BoschFSI\Repository
Delete the .bin file(s) - In Windows Control Panel / Local services
Restart the server - In FSM Client / File / Device management / Driver settings
Select the "new" panel to be connected and activate it (via right mouse click or status drop-down menu)