How to program a rex motion to shunt only

How to program a rex motion to shunt only

 This procedure allows the Request-to- Exit (REX) motion detector to shunt the door contact without tripping the strike/magnetic lock.

NOTE: The controller firmware version must be 3.34 or higher.

Disconnect the line driver from the master controller if it is administered by an administration kit.

  1. Ensure that a faceplate is connected to the controller.
  2. To enter faceplate programming:
    1. Press and hold [RESET] for two seconds and then release.
    2. Press it again for one second when the control panel starts to beep. " PASSWRD" appears on the display.
  3.  Type PAC1990 at the PASSWRD prompt.
  4. At the CMD prompt, type INST, and then press [ENT].
  5. Press [NXT] five times.The "ENTER SYS TYPE" prompt appears.
  6. Press [0][ENT][ESC].
  7. At the CMD prompt, type "D" , and then then press [ENT].
  8. Press [NXT] four times.
  9. At the "DR1 M2" prompt, type the channel number that you want to shunt.
  10. Press [ENT], and then press [ESC] twice. The door now shunts, but the lock does not release.