Correct the FPD-7024 or D7024 error: Programmed Points Exceeds Max

Correct the FPD-7024 or D7024 error: Programmed Points Exceeds Max

Possible causes and solution(s)

  • Causes

When assigning a point function to an input the FPD-7024 or D7024 panel may respond with “PRGRMMD POINTS EXCEED MAX”.  This message indicates that more than 20 input points have been assigned a point function using a Programmed Loop Response time.


  • Solution

There are two options when selecting the Loop Response time in a Point Function:

  • 1- Fast (.5 sec)
  • 2- Programmed

When selecting ‘Programmed’, an entry between 1 and 89 seconds is selected for the point response time.  A maximum of 20 points are allowed to be programmed with a response time other than fast. Once this number is exceeded the “PRGRMMD POINTS EXCEED MAX” message will appear.

The following notice may be found in the FPD-7024 or D7024 Installation guides:

Notice!

Up to 20 points can be assigned to point functions that were programmed with a response time other than Fast. If more than 20 points are assigned to functions programmed with a response time other than Fast, then an error message appears: PRGRMMD POINTS EXCEED MAX. Switching a point function from Fast to Programmed can cause this error, depending on how many points reference the point function.