Cloud VMS

Alarm Management Configuration: How to connect AVIOTEC

AVIOTEC camera is a video-based fire detector with the capability of detecting both fire and smoke in the scene, it is also fully capable of running standard IVA rules in the camera.

When smoke or fire is been detected, AVIOTEC will sent a Smoke/Fire event to the Cloud VMS Alarm Management and at the same time trigger it’s output.  Using this output status, we are able to trigger the Cloud VMS/VSaaS Alarm Management .


Please make sure that these pre-conditions are met:

You have access to a VSaaS/Cloud VMS an Alarm Management instance

The AVIOTEC camera that you want to configure is connected to the Cloud VMS Alarm Management via Remote Portal

You have activated the appropriate Alarm Management license in Remote Portal for the respective AVIOTEC camera

You are running the latest firmware for the AVIOTEC. This example was tested with: 7.82.0025.

Step-by-step guide


Limitation:

  1. There are 3 Fire profile in AVIOTEC, the default been “Fire”, this profile will not allow configuration of IVA rules in the camera. The other 2 profiles are called “Fire #1” and “Fire #2” these are profiles that works with both Fire/Smoke detection and IVA rules.  Please just use “Fire #2” profile that works with both Fire/Smoke detector and with IVA detections for Cloud VMSAlarm Management.
  2. The output (relay) of the AVIOTEC will turn on when either Smoke or Fire has been detected, it will remain on if the Smoke or Fire still visible, hence, VSaaS Alarm Management will only be triggered once in such case.  The output (relay) will reset to off when there are no Smoke or Fire visible in the scene.
  3. Regardless of how many fire spots have been detected, the output (relay) on the AVIOTEC will not retrigger when a new fire spot or smoke spot is been detected, it will remains on as long as there is one fire or smoke spot in the scene.

Below are the steps to configure both the camera and the VSaaS Alarm Management for Fire/Smoke Detection.

For details on how to setup the AVIOTEC camera for Fire/Smoke detection, please refer to the manual for details.   In the following example, we will be using “Fire #2” profile, the steps for “Fire” profile is the same, except that “Fire” profile does not allows configuration of IVA rules.

Step 1:

Goes to VCA->Main Operation.

Select “Fire #2” profile



Step 2:

Go to Fire Detection

Configure the Fire detection parameters as required.

Step 3:

Login to the VSaaS Alarm Management instance.

Navigate to the relevant site and add the device to the Cloud VMS Alarm Management (if not already done:   https://community.boschsecurity.com/t5/Security-Video/How-to-add-Remote-Portal-cameras-to-Bosch-Cloud-VMS/ta-p/49710)

Create a new VSaaS Alarm Management Service using Live Intervention.


Step 4:

Select the Trigger Device as the AVIOTEC camera, the Triggering Event as "Relay 1 ON" of the camera.

Select Always as the Arming Period.

Provide a self-explanatory Name for the service.

If there is a need to automatic or intervention actions, you will also need to configure it accordingly. Just an idea, you can create a pre-recorded voice message, such as “Fire or Smoke detected, please exit the building in an orderly manner” and use this as an audio announcement that could be triggered by the operator via the EVENTMONITOR web GUI.  

The audio file is loaded to the VSaaS Alarm Management and the action will play this audio file to any cameras in the site that has a speaker connected. This can be done using the Intervention action.


Scroll ignoreadvancedINLINEgreenINLINE

MANDATORY --> after finishing this article, if you wrote advanced content in this section , you must to manually add the "advanced" label  This action is required to indicate that this article contains ADVANCED instructions for CTS/ SG or GK.

DO NOT CHANGE ANYTHING IN THIS SECTION!

advanced section
Please contact CTS / SG or GK team to view this section from draft space, if necessaryadINLINE

IMPORTANT! --> the content itself from here will be not displayed. The content from here will be displayed only when the "ad" label will be set after article creation. Only CTS/ SG or GK are allowed to use "ad" label.

PLEASE do not set "ad" label from beginning. Use it only when you need this info and REMOVE the "ad" label when finished!

Information below is for CTS, SG, GK reference and must be kept internal only.

If you are part of CTS, SG or GK team, please hide this section when you have finished using this article!

DO NOT CHANGE ANYTHING IN THIS SECTION!

This section will not be published externally and / or automatically downloaded in the PDF file!

Type your text/ advanced information here

Please write here the statement/answer/explanation

Add pictures, if necessary





Scroll only
scroll-pdftrue
scroll-officetrue
scroll-chmtrue
scroll-docbooktrue
scroll-eclipsehelptrue
scroll-epubtrue
scroll-htmltrue


You are using an Offline Version of these Article, please ensure to regularly check the corresponding online article on the Bosch Building Technologies Knowledge Base for any updates. Use the date and version information of the document as reference.

This is  created  

Check for Updateprimaryhttps://community.boschsecurity.com/t5/Bosch-Building-Technologies/ct-p/bt_community